Nasıl Yapılır12 Mayıs 2026DOA Enerji Bakım Ekibi

Transformer Annual Maintenance Checklist: Professional Maintenance in 25 Steps

Back

Annual periodic maintenance checklist for oil-filled and dry-type transformers. Thermal, electrical and mechanical checks, oil analysis, and reporting in 25 steps.

Transformer Annual Maintenance — In Brief

Transformer annual maintenance is a 25-step standard process covering external visual inspection, thermographic scanning, insulation testing, grounding resistance measurement, protection relay testing, oil analysis (DGA, BDV, acidity), connection torque checks, and functional tests. It must be performed by authorized teams in accordance with TS HD 60364, IEEE C57.91, IEC 60076 standards. Proper annual maintenance reduces the probability of failure by 80%, extends service life by 5–10 years, and ensures the validity of the insurance policy.

Maintenance Frequency

Transformer TypeMaintenance Frequency
Oil-filled < 1 MVAOnce per year (full) + once every 6 months (visual)
Oil-filled 1–10 MVATwice per year (oil and thermal) + full overhaul once every 5 years
Oil-filled > 10 MVAOnce every 3 months (critical), full overhaul once every 3 years
Dry-type < 2.5 MVAOnce per year (full)
Dry-type > 2.5 MVAOnce every 6 months (thermal) + annual (full)

25-Step Maintenance Checklist

A. Pre-Commissioning Preparation (Steps 1–3)

Step 1: Safety Precautions

  • Switch off and lock out the transformer energy (LOTO procedure)
  • Switch labeling: “UNDER MAINTENANCE – DO NOT TOUCH”
  • Voltage check with test equipment (0 V on all 3 phases)
  • Grounding connection (temporary grounding rod)
  • Personal protective equipment (PPE): Class 2 insulating gloves, face shield, antistatic boots

Step 2: Document Check

  • Transformer nameplate data (manufacturer, serial no., kVA, kV, cooling type, vector group)
  • Previous maintenance report
  • Previous DGA results
  • Protection relay settings list

Step 3: Equipment Preparation

  • Thermal camera (FLIR or Fluke)
  • Insulation tester (5 kV Megger)
  • Tan-delta test device (in comprehensive maintenance)
  • Turns ratio test device (TTR)
  • Oil sampling kit (oil-filled type)
  • Lux meter
  • Grounding resistance tester (Earth tester)

B. Visual Inspection (Steps 4–7)

Step 4: External Visual Inspection

  • Rust, cracks, leakage traces on tank walls
  • Leak check of valves and flanges
  • Buchholz relay observation (oil-filled type)
  • Conservator level (oil level)
  • Silica gel color (dry → blue; if saturated → pink, replace)

Step 5: Bushing Inspection

  • Cracks, fractures on the porcelain surface
  • Sediment accumulation (especially in coastal facilities)
  • Leakage traces
  • Burn marks on the connection terminal

Step 6: Painted Surface Check

  • Corrosion starting points
  • Paint blistering or peeling
  • Nameplate legibility

Step 7: Cooling System Check

  • Oil-filled: are fan motors (if any) running, is oil circulation normal
  • Dry-type: are ventilation channels open, is the fan motor healthy
  • Air-conditioning/ventilation operation check

C. Electrical Tests (Steps 8–15)

Step 8: Grounding Resistance

  • Transformer body grounding resistance: ≤ 1 Ω
  • Neutral grounding resistance: ≤ 1 Ω
  • Ground electrode resistance (site): ≤ 4 Ω

Step 9: Insulation Resistance (Megger)

  • HV–LV: ≥ 1000 MΩ (at 5 kV)
  • HV–Ground: ≥ 1000 MΩ
  • LV–Ground: ≥ 100 MΩ
  • Polarization index (PI = R10min/R1min): ≥ 2.0 (adequate insulation)

Step 10: Turns Ratio Test (TTR)

  • Deviation from nominal turns ratio: ≤ ±0.5%
  • All 3 phases are tested
  • All tap positions are checked (if on-load tap changer exists)

Step 11: DC Resistance Test

  • Compare DC resistance values of all 3 phases
  • Phase-to-phase deviation: ≤ 2%

Step 12: Tan-Delta Test (In Comprehensive Maintenance)

  • Tan-delta < 1% → excellent insulation
  • Tan-delta 1–1.5% → acceptable
  • Tan-delta > 2% → replacement required

Step 13: Protection Relay Tests

  • Overcurrent relay (50/51) test currents
  • Buchholz relay (oil-filled): gas accumulation threshold
  • Temperature relay: alarm 80°C, trip 90°C (oil-filled)
  • Differential relay (87T) simulation test if present
  • REF (Restricted Earth Fault) test

Step 14: On-Load Tap Changer (LTC) Check

  • Number of operations (log record)
  • Oil quality (separate oil for LTC)
  • Switching noise and performance

Step 15: Connection Torque Check

ConnectionTorque (Nm)
M8 bushing25–30
M10 bushing50–60
M12 busbar80–100
M16 busbar200–250

D. Oil Analyses (Oil-Filled Only) (Steps 16–20)

Step 16: Oil Sampling

  • When the transformer is cool (≤ 40°C tank temperature)
  • Bottom sample (bottom valve) → acidity test
  • Top-point sample → DGA test
  • Sterile glass bottle, without contamination

Step 17: BDV Test (Dielectric Strength)

Transformer VoltageMinimum BDV
< 1 kV30 kV
1–72.5 kV50 kV
> 72.5 kV60 kV

BDV ≤ 40 kV → oil drying or replacement required

Step 18: DGA (Dissolved Gas Analysis) Monitoring of the following gases in ppm:

  • Hydrogen (H₂): partial discharge
  • Methane (CH₄): low-temperature heating
  • Ethane (C₂H₆): low-temperature heating
  • Ethylene (C₂H₄): high-temperature heating
  • Acetylene (C₂H₂): arcing discharge (CRITICAL)
  • CO and CO₂: cellulose degradation (paper insulation)

Step 19: Acidity Test

  • Oil acid number: mg KOH/g
  • New oil < 0.03
  • Maintenance limit: < 0.20
  • 0.30 → oil change is mandatory

Step 20: Moisture Test

  • Karl Fischer titration
  • < 20 ppm: good
  • 20–30 ppm: acceptable
  • 30 ppm: drying required

E. Thermographic Inspection (Steps 21–22)

Step 21: Thermal Camera Scan

  • Connection points: abnormal if above ambient by +20°C
  • Bushing terminals: temperature should be equal across all phases
  • Cooling fan motors: ambient +30°C is acceptable
  • Transformer surface temperature: 60–75°C normal range

Step 22: Load Curve Analysis

  • 24-hour load monitoring
  • Identification of peak load time
  • If overload is present, capacity increase is recommended

F. Closeout and Documentation (Steps 23–25)

Step 23: Comparison of Test Results

  • Compare with the previous year’s tests
  • Trend analysis (acidity increase, insulation drop, etc.)
  • Root cause analysis for abnormal values

Step 24: Corrective Actions

  • Corrective intervention for identified abnormalities
  • Oil change/filtration (if necessary)
  • Replacement of sealing gasket
  • Corrosion repair

Step 25: Maintenance Report

  • All test results (PDF format)
  • Thermal camera images
  • DGA chart (time series)
  • Interventions performed
  • Recommendations for the next maintenance
  • Signature: responsible maintenance engineer (registered with EMO)

Typical Maintenance Cost (TR 2026)

TransformerOil-Filled MaintenanceDry MaintenanceDGA Analysis
250 kVA9,500 TL7,500 TL1,800 TL
1000 kVA18,000 TL14,000 TL1,800 TL
2500 kVA35,000 TL28,000 TL1,800 TL

DOA Enerji Transformer Maintenance Service

DOA Enerji performs annual and periodic maintenance of your oil-filled and dry-type transformers with its engineering staff certified for MV and registered with EMO. A full test package (including DGA) in accordance with the TS HD 60364 standard, 24/7 emergency fault support, and an annual periodic maintenance contract are offered.

Frequently Asked Questions

Is the transformer de-energized during maintenance?

An outage is required for most tests (especially electrical tests). Visual and thermographic inspections can be performed while energized. For a full overhaul, a 6–12 hour outage should be planned.

Why is DGA analysis so important?

DGA dissolved gas interpretation is the transformer’s “blood test.” If acetylene is detected, it means internal arcing and the transformer must be taken out of service immediately. DGA detects 80% of critical failures early.

How often should silica gel be replaced?

When it loses its blue color and turns pink, or once per year (whichever comes first). Old silica gel can be dried in an oven at 120°C for 4 hours and reused.

Is oil analysis required for a dry-type transformer?

No. For dry-type, only thermographic inspection, insulation testing, and fan and temperature relay testing are sufficient. Oil analysis is performed only on oil-filled types.

How long does the post-maintenance report take?

After field work is completed, the DGA laboratory result takes 3–5 business days. The full report is delivered within 1 week.

We use cookies to improve your experience on our website. For more information, please see our .